GETTING STARTED MANUAL REVISION 2.0
16
Lockout Alarms
Selecting the ‘Lckout ALM’ menu option shows the first 2 Lockout alarms (Lockout alarms are a subset of
alarms):
ACTUAL DISPLAY DESCRIPTION
Passwords
Selecting the ‘Passwords’ option shows the following:
ACTUAL DISPLAY DESCRIPTION
Authorization Function
The authorization code is a special four-character code that enables access in to the Magnum system. The code
must be numeric with values between 1 and 8 if it is entered from the Keypad/Display. If the Magnum is being
accessed through MCS-Connect, the code may consist of any valid alpha/numeric characters. Each system can
have up to 15 different authorization codes. There are four levels of authorization, which provide different
capabilities within the system. The authorization codes cannot be viewed in a Magnum system. These are
established when building the configuration file in MCS-Config.
From the Keypad/Display the following changes can be made based upon the authorization level:
FUNCTION VIEW USER SERVICE SUPERVISOR FACTORY
Sensor offsets NO NO YES YES YES
Sensor diagnostics NO NO YES YES YES
Clear alarm history NO NO NO NO YES
Clear point information NO NO NO NO YES
Date and time set YES YES YES YES YES
Day of week set YES YES YES YES YES
Change No Flow Lockout or shut down NO NO NO NO YES
Change rotate Yes or No NO NO NO NO YES
Change Manual/Auto settings NO NO NO YES YES
Change setpoint values * * * * YES
Change operating schedules NO YES YES YES YES
Change holiday dates NO YES YES YES YES
Lockout Reset ** ** ** ** YES
Change RS485 network settings NO YES YES YES YES
Change Ethernet network settings NO YES YES YES YES
Adjust Keypad/Display contrast YES YES YES YES YES
* Setpoints may have individual authorization levels; you must have the proper authorization to view or edit them.
**See the Setup screen of the configuration for authorization level(s) that are allowed unlimited resets per day.
Authorization levels below ‘Auth Level Bypass’ are allowed only a limited number of resets. Authorization levels at
and above ‘Auth Level Bypass’ are allowed unlimited lockout resets.
09:56 Lckout ALM
11 ALARM CIR BREAKER
MAR 29 08:56:34
No Additional Info
Prev Next
HH:MM Screen Title
Screen will show any Lockout Alarms, including the
alarm number, name, date, and time.
Previous alarm Next
09:56 Password
Enter Pin
----
Then Press ‘ Key
HH:MM Screen Title
Enter 4 digit Password and press the enter key to gain
authorization.