AppendixA. TroubleshootingTips
AppendixA.1. ConnectingAPCtotheMCSBMSGATEWAY
Confirmthatthenetworkcablingiscorrect
Confirmthatthecomputernetworkcardisoperationalandcorrectlyconfigured
Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is
configuredtoruntheTCP/IPprotocol
CheckthattheIPnetmask
ofthePCmatchestheMCSBMSGATEWAY.TheDefaultIPAddressoftheMCS
BMSGATEWAYis192.168.10.85,SubnetMaskis255.255.255.0,DefaultGatewayis192.168.10.1.
GotoStart>Run
Typein“ipconfig”
Theaccountsettingsshouldbedisplayed
Ensure that the IP address
is 192.168.10.xxx, the Subnet mask is 255.255.255.0 and the Default
Gatewayis192.168.10.1
EnsurethatthePCandMCSBMSGATEWAYareonthesameIPNetwork,orassignaStaticIPAddressto
thePConthe192.168.10.network
IfUsingWindowsXP,ensurethatthefirewallis
disabled
EnsurethatallotherEthernetcardsactiveonthePC,especiallywirelessadaptersaredisabled
AppendixA.2. NocommunicationbetweentheMCSMagnumandtheMCSBMSGATEWAY
Confirmthatthenetworkcablingiscorrect
Check that the IP address, subnetmask, and the default gateway of the MCSMagnum match what the
labelontheMCSBMSGATEWAYsaysitshouldbesetto.
Check the LED’s on the Ethernet port. The yellow LED should be
solid yellow the green LED should
continuouslyflash.
EthernetPort
GreenLED
YellowLED