MCS‐BMS‐GATEWAYStartupGuide Revision4.0
MicroControlSystems5580EnterprisePkwy,FortMyers,FL33905USAWeb:www.mcscontrols.com
Tel:(239)6940089Fax:(239)6940031
17
4.1 Connectthe PCtotheMCS‐ BMS‐GATEWAY via theEthernetport
Figure10:EthernetportlocationofMCS‐BMS‐GATEWAY
DisableanywirelessEthernetadaptersonthePC/Laptop
Disablefirewallandvirusprotectionsoftware
Connectacrossovercat5EthernetcablebetweenthePCandMCS‐BMS‐GATEWAY
TheMCS Default IP Address oftheMCS‐BMS‐GATEWAYis 192.168.10.85,Subnet Mask is 255.255.255.0
and the default
gateway 192.168.10.1. If the PC and the MCS‐BMS‐GATEWAY are on different IP
Networks,assignastaticIPAddresstothePConthe192.168.10.xxxnetwork.
Goto>>
Right‐clickonLocalAreaConnection>Properties
Highlight>
Select: Use the following
IP address and enter an IP address, Subnet mask and default gateway on the
samenetwork(ex.Seefigurebelow)
Clicktwice
GotoStart>Programs>FieldServerUtilities>PingUtility
IftheIPAddressof the MCS‐BMS‐GATEWAY module appearsonthe
screen,the MCS‐BMS‐GATEWAYis
running (See Figure 16: Ping utility). If the module does not appear on the Ping Utility we may have an
issuewiththeIPaddress.IfthisisthecasetrythefollowingsettingsonyourPC’slocalareaconnection.IP
Address192.168.1.xxx(any available address
other then 192.168.1.24), Subnet Mask is 255.255.255.0
andthedefaultgateway192.168.1.1.
EthernetPort
Vista de pagina 16