MAGNUM VERSION 8 MANUAL REVISION 3.1
110
In the above example if relay ‘RUN’ is OFF, the value of this Analog Output will be zero. If ON, the value will be
calculated based on the Sensor Input ‘ChilWtrOut’. If ‘ChilWtrOut’s value is 40 (or less) then the Analog Output will be
set to 0%; If 60 (or above) then the Analog Output will be 100%. The output value will vary based on a linear
calculation between these two points.